Fault, Causes and Remedies for: Induction Motor |
|||
Fault Heading |
Fault |
Causes |
Remedies |
Induction motor |
1) Motor does not start on load. |
a) No supply voltage |
a) Check voltage at Motor Terminals. |
b) Driven equipment jam |
b) Ensure freeness of driven equipment. |
||
c) Motor shaft jammed. |
c) Check freeness of motor shaft. |
||
2) Motor starts and gets trips (star delta starter) |
a) Timer setting on lowest step |
a) Set timer on proper setting. |
|
b) Relay setting on lower reading than rated current. |
b) Set overload relay at 110% of rated full load current punched on Nameplate. |
||
c) Terminal voltage is low. |
c) Ensure rated voltage OR increase realy setting slightly. |
||
d) Backup fuse blowing. |
d) Correct rating of back-up fuse to be used. |
||
e) Starting current is high due to heavy inertia. |
e) Start stop the relay continously till motor, pick up full speed. If problem persist, Contact Us and inform Gd2 of load. |
||
f) Misalignment. |
f) Ensure proper alignment. |
||
3) Motor connected but does not picks up full speed. |
a) No supply of voltage |
a) Check voltage between each two phases. |
|
b) Motor jam |
b) Check freeness of motor without coupling it to load. |
||
c) Motor may be overloaded |
c) Reduce load. |
||
d) Loose connection. |
d)Tight connection properly. |
||
4) Motors runs and then stops |
a) Power failure |
a) Check loose connection to the line of fuses and starter in the motor Terminals. |
|
b) Unbalance incoming 3 Phase voltage to motor. |
b)1) Check loose connection. 2)Check the unbalance voltage and inform to Electricity Board people. c)Check all 3 fuses are proper rating. |
||
c) Overload |
c) Examine overload relay and see that they are set correctly to approximately 110% full load current punched on nameplate. |
||
5) Motor does not achieve full speed. |
a) Wrong KW / HP Selection. |
a) Consult supplier for proper type of motor. |
|
b) Voltage too low at motor terminals because voltage drop. |
b) Use higher voltage tap on transformer terminals or increase cable size. |
||
c) Starting load too high. |
c) Reduce load, check the load, motor is supposed to start. |
||
d) Wrong connection. |
d) Do the connection as per connection diagram provided inside the Terminal box. |
||
6) Motor takes too long to accelerate |
a) Excess loading |
a) Reduce load if motor is driving a heavy load or select higher rating motor |
|
b) Applied voltage too low |
b) Contact Electric Board to increase voltage tap. |
||
b) Centrifugal switch open. |
b) Check contact of centrifugal switch. |
||
7) Winding burnt due to single phasing |
a) Faulty starter (All 3 contact strip may not contact properly.) |
a) Replace the starter. |
|
b) Discontinuity in cable/cable short. |
b) 1)Replace the cable. 2)Use single phase preventor. |
||
c) One fuse blown |
c) Replace fuse of correct rating. |
||
d) Loose connection in starter or motor. |
d) Ensure proper tightness of connection. |
||
8) Wrong rotation |
a) Wrong sequence of phases. |
a) Reverse any two leads (phase)connections of motor or at switch board. |
|
9) Motor not running incase of duel speed motor. |
a) Connection not as per diagram provided. |
a) Do connection as per connection diagram given inside the Terminal Box. |
|
10) Motor shaft not free |
a) Fan not rotating due to touching with Fancover. |
a) Replace Fan / Fancover. |
|
b) Dust, dirt and foreign particle got stuck between the Oilseal / O ring seal and shaft. |
b) Remove the dust, dirt and foreign particles. |
||
c) Rotor endrings fins obstructing with bearing cover nuts due to bearing cover fitted wrongly. |
c) Open the motor and refit. Open the motor and refit the bearing cover correctly. |
||
11) Excess Full Load current. |
a) Excess loading. |
a) Consult equipment manufacturer to ensure correct HP. |
|
b) Low voltage |
b) Ensure voltage at motor terminal as per nameplate details. |
||
c) Driven Equipment jammed. |
c) Contact equipment manufacturer. |
||
d) Contact strip of starter rusty. |
d) Replace starter. |
||
e) Misalignment |
e) Ensure proper alignment. |
||
12) Excess no load current |
a) Load of mechanism coming on motor. |
a) De-couple the motor from the mechanism verify the current with Test Certificates. |
|
b) The range of instrument selected for Checking the current is not suitable. |
b) Select instrument having range 2 to 3 times of value to be measured. |
||
c) Voltage at motor Terminals may be more than rated voltage of motor. |
c) Correct the supply voltage by auto transformer. |
||
d) Supply frequency less than rated frequency of motor. |
d) Check the supply frequency and correct the supply voltage at terminals by using following formula at 50hz-415v site frequency. Test volts = (415 x 50)/(Supply Frequency) |
||
e) Unbalance supply voltage. |
e) While run in full load, the current should be within the rated value. |
||
f) Loose connection in supply cables. |
f) Locate and tightened a screw. |
||
g) Wrong connection in stator. |
g) Correct the connection. |
||
13) Abnormal unbalanced current in 3 phases. |
a) Unbalanced voltage. |
a) Please correct voltage balance in all 3 phases and connected load. 2)Loose connection at starter. 3)Ensure fuses are proper size in all 3 phases. |
|
14) Motor overheates while running on load. |
a) Overload |
a) Reduce load / overload protection to be given. |
|
b) Fan blades may clogged with dirt and improper ventilation to motor. |
b) Ensure the Cleaning of fan and continuous circulation of air over the motor for proper cooling. |
||
c) Motor may have one phase open |
c) Ensure that all leads are well connected and 3 phases supply is available. |
||
15) Noise |
a) Foundation is not Rigid. |
a) Ensure rigidity. |
|
b) Belt pulley misalignment. |
b) Correct the alignment. |
||
c) Noise due to solidification of Grease. |
c) Remove the grease and re-apply the new high temperature grease or replace the bearing. |
||
d) Noise due to driven equipment. |
d) Check noise level of Bare motor. |
||
e) Noise due to water / oil ingress into the bearings. |
e) Change Oilseal to avoid liquid ingress into the Bearing. |
||
f) Bearing noise due to punchmarks in bearing housing by unauthorised person. |
f) Replace Flange OR Endcover. |
||
g) Humming noise in motor |
g) Certain amount of magnetic noise is inherent in some low speed design motor. |
||
16) Motor vibrates after connection have been made. |
a) Motor misaligned |
a) Re-align |
|
b) Coupling between driven member and motor shaft is out of balance. |
b) Balance the coupling. |
||
c) Driven equipment un-balanced or balanced with full key. |
c) Rebalance drivenequipment or balance with half key. |
||
d) Defective ball bearing. |
d) Replace bearings. |
||
e) Vibration due to fancover touches Bottom. |
e) Ensure that there is a gap of 1 mm between fancover and base. |
||
17) Shaft broken --- |
a) Misalignment of pulley. |
a) Ensure proper alignment of motor and driven equipment. |
|
b) Impact / sudden load or sudden reversal of direction or no. of start / stops are more than 6 per hour. |
b) Please inform during procurement of motor to select suitable shaft material with proper heat treatment. |
||
c) Foundation not rigid. |
c) Make foundation rigid. |
||
d) Fixed coupling. |
d) Use flexible coupling if there is slight misalignmnet. |
||
e) Rework like drilling, punching and hammering on shaft extension. |
e) Replace Rotor Shaft. |
||
18) Shaft runout. |
a) Shaft bent / twisted. |
a) If runout of shaft is more than 40 um, replace shaft. |
|
19) Starting speed less or motor does not start in Single Phase motor. |
a) Loose connection of capacitor in Terminal Box. |
a) Ensure the tight connection of capacitor in circuit as per connection diagram. |
|
20) Motor rotating in both direction in Single Phase Motor. |
a) Capacitor failure. |
a) Replace capacitor. |
|
21)Problem related to Brake. |
a) -------- |
a) Contact us. |